Protective Relaying by Equipment
The protective functions commonly applied to transformers, motors, generators, buses, feeders and capacitor banks, and the IEEE guide behind each.
Transformer IEEE C37.91 (guide for protecting power transformers)
| 87T | Differential — internal faults, with harmonic restraint for inrush. |
| 50/51 | Phase overcurrent on the primary as backup and through-fault protection. |
| 51G / 50N/51N | Ground overcurrent on the neutral or residual, per winding grounding. |
| 63 / 63SPR | Sudden pressure or gas (Buchholz) relay for liquid-filled units. |
| 49 / 26 | Winding or oil temperature. |
| 24 | Volts per hertz where overexcitation is possible (generator step-up units). |
Small distribution transformers are commonly protected by fuses or overcurrent alone; differential is typical from roughly 5 to 10 MVA upward.
Induction motor IEEE C37.96 (guide for AC motor protection)
| 49 / 51 | Thermal overload model and locked-rotor or long-start protection. |
| 50 | Instantaneous phase overcurrent for short circuits (not with contactor-only interruption beyond its rating). |
| 50G / 51G | Ground fault, often from a zero-sequence (window) CT. |
| 46 | Current unbalance or negative sequence, including single phasing. |
| 27 / 59 | Under- and overvoltage. |
| 66 / 48 | Starts per hour and incomplete sequence. |
| 37 | Undercurrent or underpower, for pumps running dry or broken couplings. |
| 38 / 49R | Bearing and stator RTD temperatures on larger machines. |
| 87M | Differential for large or critical motors. |
Low-voltage motors usually rely on the starter overload relay and the branch circuit device; the full list applies to medium-voltage motors.
Generator IEEE C37.102 (guide for AC generator protection)
| 87G | Stator differential. |
| 64G / 59N / 27TN | Stator ground fault; 59N covers most of the winding, third-harmonic 27TN extends coverage to the neutral end. |
| 40 | Loss of field (excitation). |
| 32 | Reverse power, protecting the prime mover from motoring. |
| 46 | Negative-sequence current heating the rotor. |
| 51V / 21 | Voltage-restrained overcurrent or distance as backup for system faults. |
| 24 | Overexcitation (volts per hertz). |
| 81O/U | Over- and underfrequency. |
| 59 / 27 | Over- and undervoltage. |
| 78 | Out-of-step for large machines on strong systems. |
Emergency and standby sets under NFPA 110 often use a reduced set with alarms instead of trips for some functions.
Bus IEEE C37.234 (guide for protective relay applications to power system buses)
| 87B | Bus differential (low- or high-impedance). |
| 50/51 partial differential | Summed source currents as a lower-cost alternative. |
| 50BF | Breaker failure, clearing the bus when a feeder breaker fails to open. |
| Zone interlocking | Fast bus tripping by blocking signals from feeder relays. |
Arc-flash reduction often drives faster bus protection (differential, zone interlocking or maintenance switch).
Feeder and line IEEE C37.230 (distribution lines), C37.113 (transmission lines)
| 50/51 | Phase overcurrent, coordinated with downstream devices. |
| 50N/51N or 50G/51G | Ground overcurrent. |
| 67 / 67N | Directional overcurrent in looped or multi-source systems. |
| 79 | Automatic reclosing on overhead lines. |
| 21 | Distance protection on transmission and sub-transmission lines. |
| 87L | Line current differential over a communication channel. |
Radial industrial feeders usually need only 50/51 and ground protection; directional and pilot schemes appear with multiple sources.
Capacitor bank IEEE C37.99 (guide for protection of shunt capacitor banks)
| 50/51 | Bank overcurrent for major faults. |
| 60 / 59N unbalance | Unbalance detection for failed units or elements. |
| 59 / 27 | Overvoltage, and undervoltage to trip before re-energizing a charged bank. |
Fuses (external or internal) protect individual capacitor units.
Sources: IEEE C37.2 (device numbers) and the IEEE C37 application guides named on each card — described in our own words. © RokBench.