ANSI Device Numbers
33 device function numbers that appear most often on single-line diagrams and relay settings, with what each one does.
- 2Time-delay starting or closing relay
Adds a set delay before an operation in a sequence.
- 21Distance relay
Trips when the impedance seen from the relay falls inside a set reach — used on transmission lines.
- 24Volts per hertz relay
Protects transformers and generators from overexcitation.
- 25Synchronism-check relay
Permits closing only when voltage, frequency and phase angle on both sides match closely enough.
- 27Undervoltage relay
Operates when voltage falls below a setting; used for load shedding, transfer and motor protection.
- 32Directional power relay
Detects power flowing the wrong way, such as a generator motoring or export past a utility interconnection.
- 38Bearing protective device
Responds to excessive bearing temperature.
- 40Loss-of-field relay
Detects loss of generator excitation.
- 46Negative-sequence (phase-balance) current relay
Protects rotating machines from heating caused by unbalanced or single-phased supply.
- 47Phase-sequence or phase-balance voltage relay
Blocks or trips on reversed phase rotation or unbalanced voltage.
- 49Thermal relay
Models or measures equipment temperature, typically motor or transformer overload.
- 50Instantaneous overcurrent relay
Trips without intentional delay above a current setting.
- 50BFBreaker failure
Trips backup breakers if the primary breaker does not clear a fault in time.
- 51AC time-overcurrent relay
Trips after a delay that shortens as current rises (an inverse curve).
- 50N / 51N, 50G / 51GGround (neutral) overcurrent
Overcurrent elements applied to residual or ground current. The suffix identifies how the current is measured.
- 52AC circuit breaker
The breaker itself; 52a and 52b are its auxiliary contacts that follow and oppose its position.
- 59Overvoltage relay
Operates when voltage rises above a setting.
- 59NNeutral overvoltage
Detects ground faults on ungrounded or high-resistance-grounded systems from neutral displacement.
- 60Voltage or current balance relay
Compares two circuits, often to detect a blown VT fuse.
- 62Time-delay stopping or opening relay
Adds a delay to an opening or stopping sequence.
- 63Pressure switch
Responds to gas or liquid pressure; on transformers, the sudden-pressure relay.
- 64Ground detector relay
Detects insulation failure to ground, for example 64G on generator stator windings.
- 67AC directional overcurrent relay
Overcurrent protection that operates only for current flowing in a chosen direction.
- 68Blocking relay
Blocks tripping or reclosing under set conditions, such as power swings.
- 74Alarm relay
Drives an alarm rather than a trip.
- 78Phase-angle or out-of-step relay
Detects loss of synchronism.
- 79Reclosing relay
Recloses a breaker automatically after a trip, usually on overhead lines.
- 81Frequency relay
Operates on under- or over-frequency (81U / 81O), for load shedding and generator protection.
- 83Automatic selective control or transfer relay
Selects between sources or conditions automatically.
- 86Lockout relay
Trips and holds breakers open until manually reset, so equipment is not re-energized into a fault.
- 87Differential protective relay
Compares current entering and leaving a zone (transformer 87T, bus 87B, generator 87G, line 87L) and trips for faults inside it.
- 89Line switch
A disconnect or load-break switch.
- 94Tripping or trip-free relay
Trips a breaker or prevents it from reclosing.
Source: IEEE Std C37.2 (device function numbers), described in our own words. © RokBench.