Reference / Max Cable Length
Quick reference · Grade G

Maximum Cable Length

How far each conductor size can run before the voltage drop reaches 3%, expressed as ampere-feet: divide by the load current to get the maximum one-way length.

Copper ampere-feet for 3% voltage drop, one-way length

Size120 V 1φ208 V 3φ277 V 1φ480 V 3φ
14 AWG5861,1731,3532,707
12 AWG9321,8652,1514,304
10 AWG1,4822,9663,4206,844
8 AWG2,3564,7165,43910,882
6 AWG3,7467,4988,64817,304
4 AWG5,95711,92313,75127,514
3 AWG7,51215,03417,33934,694
2 AWG9,47218,95821,86443,749
1 AWG11,94423,90527,57055,166
1/0 AWG15,06130,14434,76669,563
2/0 AWG18,99138,01143,83987,718
3/0 AWG23,94847,93155,279111k
4/0 AWG30,19860,44069,706139k
250 kcmil35,67871,40882,356165k
300 kcmil42,81385,69098,827198k
350 kcmil49,94999,971115k231k
400 kcmil57,084114k132k264k
500 kcmil71,355143k165k330k
600 kcmil85,626171k198k395k
700 kcmil99,897200k231k461k
750 kcmil107k214k247k494k
800 kcmil114k229k264k527k
900 kcmil128k257k296k593k
1000 kcmil143k286k329k659k

Aluminum ampere-feet for 3% voltage drop, one-way length

Size120 V 1φ208 V 3φ277 V 1φ480 V 3φ
12 AWG5661,1331,3062,614
10 AWG9001,8012,0774,156
8 AWG1,4312,8643,3036,608
6 AWG2,2754,5535,25110,508
4 AWG3,6177,2408,35016,708
3 AWG4,5619,13010,52921,068
2 AWG5,75211,51213,27726,567
1 AWG7,25314,51716,74233,500
1/0 AWG9,14618,30521,11142,243
2/0 AWG11,53323,08226,62153,267
3/0 AWG14,54229,10633,56967,168
4/0 AWG18,33836,70242,32984,698
250 kcmil21,66543,36350,011100k
300 kcmil25,99852,03560,013120k
350 kcmil30,33260,70870,015140k
400 kcmil34,66569,38080,017160k
500 kcmil43,33186,726100k200k
600 kcmil51,997104k120k240k
700 kcmil60,663121k140k280k
750 kcmil64,996130k150k300k
800 kcmil69,329139k160k320k
900 kcmil77,995156k180k360k
1000 kcmil86,661173k200k400k

Calculated by RokBench from standard conductor resistivity and temperature coefficients (100% IACS copper, 61% IACS aluminum). © RokBench.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.