Reference / Full-Load Current
Quick reference · Grade G

Full-Load Current

Line current from kVA, kW and HP at common single- and three-phase voltages.

Motor currents below are calculated. They are not the NEC motor full-load current table values, which conductor and protection sizing for motors must use (NEC 2023 430.6(A)(1)).

Three-phase, from kVA amperes

kVA208 V240 V480 V600 V4,160 V13,800 V
1541.636.118.014.42.10.6
3083.372.236.128.94.21.3
4512510854.143.36.21.9
7520818090.272.210.43.1
112.531227113510815.64.7
15041636118014420.86.3
22562554127121731.29.4
30083372236128941.612.6
5001,3881,20360148169.420.9
7502,0821,80490272210431.4
10002,7762,4061,20396213941.8
15004,1643,6081,8041,44320862.8
20005,5514,8112,4061,92527883.7
25006,9396,0143,0072,406347105
30008,3277,2173,6082,887416126

Single-phase, from kVA amperes

kVA120 V240 V
1083.341.7
1512562.5
25208104
37.5313156
50417208
75625313
100833417
1671,392696

Three-phase 480 V, from kW amperes by power factor

kWPF 0.80PF 0.85PF 0.90PF 1.00
11.51.41.31.2
57.57.16.76.0
1015.014.213.412.0
2537.635.433.430.1
5075.270.866.860.1
7511310610090.2
100150142134120
150226212200180
200301283267241
300451425401361
500752708668601

Three-phase 460 V, from HP (PF 0.85, η 0.9 assumed) amperes — not NEC table values

HPCalculated A
11.2
22.4
56.1
1012.2
1518.4
2024.5
2530.6
3036.7
4048.9
5061.2
7591.8
100122
150184
200245

Computed from the power formulas above. © RokBench.