Reference / Approach Distances
Quick reference · Grade G
Minimum Approach Distances (OSHA)
How close qualified employees may come to exposed energized parts during power generation, transmission and distribution work.
72.5 kV and less — Table R-6 worksites at 900 m (3,000 ft) or lower
| Nominal voltage, phase to phase (kV) | Phase-to-ground | Phase-to-phase |
|---|---|---|
| 0.050 to 0.300 | Avoid contact | |
| 0.301 to 0.750 | 0.33 m · 1.09 ft | 0.33 m · 1.09 ft |
| 0.751 to 5.0 | 0.63 m · 2.07 ft | 0.63 m · 2.07 ft |
| 5.1 to 15.0 | 0.65 m · 2.14 ft | 0.68 m · 2.24 ft |
| 15.1 to 36.0 | 0.77 m · 2.53 ft | 0.89 m · 2.92 ft |
| 36.1 to 46.0 | 0.84 m · 2.76 ft | 0.98 m · 3.22 ft |
| 46.1 to 72.5 | 1.00 m · 3.29 ft | 1.20 m · 3.94 ft |
More than 72.5 kV — Table R-7 worksites at 900 m (3,000 ft) or lower
| Nominal voltage, phase to phase (kV) | Phase-to-ground | Phase-to-phase |
|---|---|---|
| 72.6 to 121.0 | 1.13 m · 3.71 ft | 1.42 m · 4.66 ft |
| 121.1 to 145.0 | 1.30 m · 4.27 ft | 1.64 m · 5.38 ft |
| 145.1 to 169.0 | 1.46 m · 4.79 ft | 1.94 m · 6.36 ft |
| 169.1 to 242.0 | 2.01 m · 6.59 ft | 3.08 m · 10.10 ft |
| 242.1 to 362.0 | 3.41 m · 11.19 ft | 5.52 m · 18.11 ft |
| 362.1 to 420.0 | 4.25 m · 13.94 ft | 6.81 m · 22.34 ft |
| 420.1 to 550.0 | 5.07 m · 16.63 ft | 8.24 m · 27.03 ft |
| 550.1 to 800.0 | 6.88 m · 22.57 ft | 11.38 m · 37.34 ft |
Altitude correction — Table R-5 multiply the distances above by A
| Altitude above sea level | A |
|---|---|
| 0 to 900 m | 1.00 |
| 901 to 1,200 m | 1.02 |
| 1,201 to 1,500 m | 1.05 |
| 1,501 to 1,800 m | 1.08 |
| 1,801 to 2,100 m | 1.11 |
| 2,101 to 2,400 m | 1.14 |
| 2,401 to 2,700 m | 1.17 |
| 2,701 to 3,000 m | 1.20 |
| 3,001 to 3,600 m | 1.25 |
| 3,601 to 4,200 m | 1.30 |
| 4,201 to 4,800 m | 1.35 |
| 4,801 to 5,400 m | 1.39 |
| 5,401 to 6,000 m | 1.44 |
Source: 29 CFR 1910.269(l), Tables R-5, R-6 and R-7. © RokBench.