Methods / Tray Fill
How RokBench checks this
Tray Fill
Occupancy of a cable tray, by area and by width.
1. What this check does
Reports how much of the tray cross-section the cables occupy, and how much of the tray width they would take in a single layer. Calculated in your browser.
2. Inputs used
- Tray inside width and usable depth.
- Outside diameter and quantity of each cable.
3. Formulas and assumptions
Area used
Width used
W tray inside width, H usable depth.
Symbols
| Cable outside diameter and count of type i | in or mm | |
| Tray inside width | in or mm | |
| Usable tray depth | in or mm |
- Round cables; no allowance for spacing or maintained spacing.
4. What is NOT checked
- Allowable fill, which depends on cable type, size, voltage and tray type.
- Tray load rating and support spacing.
- Ampacity in tray.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- NEC 2023 392.22 — number of conductors or cables
- NEMA VE 1 / VE 2 — tray manufacture and installation
6. Validation cases
No worked example with a published answer is registered for this page yet. Have one we should add? Use the Feedback link. All cases: Validation.
7. Known issues and changes
See the Engineering Notes. Try the tool: Tray Fill.