Methods / Transformer Short-Circuit
How RokBench checks this

Transformer Secondary Short-Circuit

A screening estimate of bolted fault current at the transformer secondary terminals.

1. What this check does

Estimates the symmetrical bolted three-phase fault current at the transformer secondary terminals and, if you enter one, compares it with the equipment rating.

2. Inputs used

3. Formulas and assumptions

Full-load current
IFL=kVA×10003 VI_{FL} = \dfrac{\mathrm{kVA} \times 1000}{\sqrt{3}\,V}
Infinite bus
ISC=IFLZ%/100I_{SC} = \dfrac{I_{FL}}{Z\%/100}
Source impedance
Zs%=kVAMVASC×1000×100Z_s\% = \dfrac{\mathrm{kVA}}{\mathrm{MVA}_{SC} \times 1000} \times 100

On the transformer base.

Finite source
ISC=IFL(Z%+Zs%)/100I_{SC} = \dfrac{I_{FL}}{\bigl(Z\% + Z_s\%\bigr)/100}
Motor contribution
IM=4 kVAM×10003 VI_M = 4\,\dfrac{\mathrm{kVA}_M \times 1000}{\sqrt{3}\,V}

Low-voltage motors, about four times rated current (IEEE 141 / 242 practice).

Asymmetry
Iasym=I1+2e−2π/(X/R)Ipeak=2 I(1+e−π/(X/R))I_{\text{asym}} = I\sqrt{1 + 2e^{-2\pi/(X/R)}} \qquad I_{\text{peak}} = \sqrt{2}\,I\left(1 + e^{-\pi/(X/R)}\right)
Regulation
VR%=%Rcos⁡φ+%Xsin⁡φ+(%Xcos⁡φ−%Rsin⁡φ)2200\mathrm{VR}\% = \%R\cos\varphi + \%X\sin\varphi + \dfrac{(\%X\cos\varphi - \%R\sin\varphi)^2}{200}

%R = Z%/√(1+(X/R)²), %X = %R·X/R. Full load, lagging power factor.

Symbols
kVA\mathrm{kVA}Transformer ratingkVA
VVSecondary line-to-line voltageV
IFLI_{FL}Secondary full-load currentA
Z%Z\%Transformer impedance on its own base%
MVASC\mathrm{MVA}_{SC}Available utility short-circuit levelMVA
Zs%Z_s\%Utility source impedance on the transformer base%
ISCI_{SC}Symmetrical three-phase fault current at the secondaryA
kVAM, IM\mathrm{kVA}_M,\ I_MRunning motors on the secondary; their fault contributionkVA, A
X/R, %R, %XX/R,\ \%R,\ \%XTransformer X/R and its resistance and reactance in percent
φ, VR%\varphi,\ \mathrm{VR}\%Load power factor angle; voltage regulation no load to full load°, %
One-line from utility source through transformer to a fault on the secondary bus, with the equivalent circuit of source impedance and transformer percent impedance in series.
Figure 1. Source impedance and transformer impedance in series up to the fault.

4. What is NOT checked

5. Reference standards

6. Validation cases

Hand-calculated cases run on every change. See Validation.

7. Known issues and changes

See the Engineering Notes. Try the tool: Transformer Secondary Short-Circuit.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.