Methods / Transformer Short-Circuit
How RokBench checks this
Transformer Secondary Short-Circuit
A screening estimate of bolted fault current at the transformer secondary terminals.
1. What this check does
Estimates the symmetrical bolted three-phase fault current at the transformer secondary terminals and, if you enter one, compares it with the equipment rating.
2. Inputs used
- Transformer kVA, secondary line-to-line voltage, nameplate impedance %Z.
- Optional: available fault level of the source in MVA; equipment interrupting or short-circuit rating in kA; transformer X/R and load power factor (regulation and asymmetry); running motor kVA on the secondary (motor contribution).
3. Formulas and assumptions
Full-load current
Infinite bus
Source impedance
On the transformer base.
Finite source
Motor contribution
Low-voltage motors, about four times rated current (IEEE 141 / 242 practice).
Asymmetry
Regulation
%R = Z%/√(1+(X/R)²), %X = %R·X/R. Full load, lagging power factor.
Symbols
| Transformer rating | kVA | |
| Secondary line-to-line voltage | V | |
| Secondary full-load current | A | |
| Transformer impedance on its own base | % | |
| Available utility short-circuit level | MVA | |
| Utility source impedance on the transformer base | % | |
| Symmetrical three-phase fault current at the secondary | A | |
| Running motors on the secondary; their fault contribution | kVA, A | |
| Transformer X/R and its resistance and reactance in percent | ||
| Load power factor angle; voltage regulation no load to full load | °, % |
- The infinite-bus result is the upper bound for the transformer alone.
- Source and transformer impedances are added as magnitudes, which assumes similar X/R ratios. This is a screening simplification.
- Motor contribution is about four times the rated current of the running motors, the common screening value; the equipment rating is compared with the total.
- Asymmetry uses the transformer X/R for the whole path; regulation is the full-load value at the power factor entered.
- Nameplate impedance is used as given. Actual impedance may be lower within manufacturing tolerance, which increases fault current.
4. What is NOT checked
- Secondary cable and bus impedance downstream of the terminals.
- X/R multiplying factors against breaker test ratings (see Short-Circuit Duty), single-phase and ground faults.
- Arc-flash incident energy and protective device coordination.
5. Reference standards
- NEC 2023 110.9, 110.10 — interrupting rating and circuit impedance
- IEEE Std C57.12.00 — transformer impedance tolerance
6. Validation cases
Hand-calculated cases run on every change. See Validation.
7. Known issues and changes
See the Engineering Notes. Try the tool: Transformer Secondary Short-Circuit.