Methods / Power Factor Correction
How RokBench checks this

Power Factor Correction

Sizing shunt capacitors for a target power factor, and the cautions that come with them.

1. What this check does

Computes the reactive power a shunt capacitor bank must supply to raise a load from its present power factor to a target, and the resulting apparent power and line current.

2. Inputs used

3. Formulas and assumptions

Capacitor kVAR
Qc=P (tan⁡φ1−tan⁡φ2),φ=arccos⁡(PF)Q_c = P\,\bigl(\tan\varphi_1 - \tan\varphi_2\bigr), \qquad \varphi = \arccos(\mathrm{PF})
Apparent power
S=PPFS = \dfrac{P}{\mathrm{PF}}
Current
I=S×10003 VI = \dfrac{S \times 1000}{\sqrt{3}\,V}

Three-phase, kVA and V line-to-line.

Symbols
PPReal power, unchanged by correctionkW
φ1, φ2\varphi_1,\ \varphi_2Power factor angle before and after correction°
QcQ_cCapacitor ratingkVAR
SSApparent powerkVA
VVLine-to-line voltageV
IILine currentA
Two overlapping power triangles sharing the kW side; the capacitor kVAR reduces kVAR from Q1 to Q2 and the angle from phi1 to phi2.
Figure 1. Capacitor kVAR shortens the reactive side of the triangle.
One-line with transformer, bus, capacitor bank and a VFD load, with a note on parallel resonance.
Figure 2. Where the capacitor sits, and why harmonics matter.

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

No worked example with a published answer is registered for this page yet. Have one we should add? Use the Feedback link. All cases: Validation.

7. Known issues and changes

See the Engineering Notes. Try the tool: PF Correction.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.