Lightning Risk Assessment
The simplified frequency comparison used to decide whether a structure needs lightning protection.
1. What this check does
Computes the equivalent collection area of a rectangular structure, the expected annual number of direct strikes and the tolerable annual number, and recommends protection when the expected exceeds the tolerable.
2. Inputs used
- Structure length, width and height.
- Ground flash density Ng, or thunderstorm days Td when Ng is unknown.
- Location factor C1 and consequence factors C2 to C5, which you select from the tables in the standard you apply.
3. Formulas and assumptions
Area within 3H of the structure.
Only when flash density is unknown.
Nt = total flash density (NASA LIS/OTD), λ = latitude. The default uses Z = 2 (Nt/3), the smallest Z of the formula, which is conservative; the latitude value of Z is offered as an option.
Strikes per year.
Protection recommended when Nd > Nc.
Level IV if E ≤ 0.80, III ≤ 0.90, II ≤ 0.95, I ≤ 0.98, I plus additional measures above 0.98.
Symbols
| Structure length, width, height | m | |
| Equivalent collection area | m² | |
| Ground flash density | flashes/km²/yr | |
| Thunderstorm days | days/yr | |
| Total (cloud + ground) flash density; cloud-to-ground ratio; latitude | flashes/km²/yr, —, ° | |
| Location factor (surroundings) | ||
| Construction, contents, occupancy and consequence factors | ||
| Expected and tolerable strike frequency | per yr | |
| Required interception efficiency of the protection system |
- Rectangular plan and a flat roof; for complex shapes use the largest applicable area.
- The factor values come from the tables of NFPA 780 Annex L or IEC 62305-2. RokBench does not reproduce those tables.
- Measured ground flash density should be preferred to the thunderstorm-day estimate.
- The coordinate estimate takes the NASA LIS/OTD satellite climatology (total lightning in 0.5° cells, no data beyond 75° latitude) and keeps one third as cloud-to-ground flashes. It is a screening value; a ground-network measurement (for example NLDN in the US) or the map in the applicable standard takes precedence.
4. What is NOT checked
- The full IEC 62305-2 risk components (loss of life, service, heritage, economic value).
- Strikes to incoming service lines and nearby structures.
- Design of the protection system itself (air terminals, down conductors, grounding, surge protection).
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- NFPA 780 (2023), Annex L — lightning risk assessment
- IEC 62305-2 — risk management
- IEC 61024-1-1:1993 — selection of protection level by efficiency (superseded by IEC 62305, still the common screening method)
- NFPA 780 and IEC 62305-3 — protection system design
- NASA LIS/OTD 0.5° High Resolution Full Climatology V2.3.2015, GHRC DAAC (doi:10.5067/LIS/LIS-OTD/DATA311)
- Prentice, S. A. and Mackerras, D. (1977), J. Appl. Meteor. 16, 545–550 — ratio of cloud to ground flashes
6. Validation cases
These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.
Rectangular structure 30 × 20 m, 10 m high lightning/risk · Hand calculation
PassSource: Hand calculation from the published collection-area and frequency equations (NFPA 780 Annex L) — Ae = 30·20 + 6·10·(30+20) + 9π·10² = 6427.4 m²; Nd = 4 · 6427.4 · 1 · 1e-6 = 0.02571; Nc = 1.5e-3. E = 1 − 0.0015/0.025710 = 0.94166 → protection level II.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| collectionAreaM2 | 6427.4 | 6427.4 | 0% | Pass |
| expectedFrequency | 0.02571 | 0.02571 | 0% | Pass |
| tolerableFrequency | 0.0015 | 0.0015 | 0% | Pass |
| requiredEfficiency | 0.941656 | 0.9417 | 0.005% | Pass |
7. Known issues and changes
See the Engineering Notes. Try the tool: Lightning Risk Assessment.