Methods / Lightning Risk
How RokBench checks this

Lightning Risk Assessment

The simplified frequency comparison used to decide whether a structure needs lightning protection.

1. What this check does

Computes the equivalent collection area of a rectangular structure, the expected annual number of direct strikes and the tolerable annual number, and recommends protection when the expected exceeds the tolerable.

2. Inputs used

3. Formulas and assumptions

Ae = L·W + 6H(L + W) + 9πH² (area within 3H of the structure) Ng ≈ 0.1 · Td (only when flash density is unknown) Nd = Ng · Ae · C1 · 10⁻⁶ expected strikes per year Nc = 1.5 × 10⁻³ / (C2 · C3 · C4 · C5) tolerable strikes per year Protection recommended when Nd > Nc

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

Hand-calculated cases run on every change. See Validation.

7. Known issues and changes

See the Changelog. Try the tool: Lightning Risk Assessment.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.