Methods / Lumen Method
How RokBench checks this

Illuminance (Lumen Method)

The lumen (zonal cavity) method for average maintained illuminance and luminaire count.

1. What this check does

Computes the room cavity ratio, the number of luminaires needed for the target average maintained illuminance, a near-square grid that fits the room, and the illuminance that grid delivers. Optionally checks spacing against the luminaire spacing criterion and reports lighting power density.

2. Inputs used

3. Formulas and assumptions

Cavity height
hrc=Hceiling−hwork plane−hsuspensionh_{rc} = H_{\text{ceiling}} - h_{\text{work plane}} - h_{\text{suspension}}
Room cavity ratio
RCR=5 hrc (L+W)L W\mathrm{RCR} = \dfrac{5\,h_{rc}\,(L + W)}{L\,W}
Luminaires
N=⌈E AΦ⋅CU⋅LLF⌉N = \left\lceil \dfrac{E\,A}{\Phi\cdot \mathrm{CU}\cdot \mathrm{LLF}} \right\rceil
Grid
c=roundN LWr=⌈Nc⌉Eachieved=r c Φ⋅CU⋅LLFAc = \mathrm{round}\sqrt{N\,\dfrac{L}{W}} \qquad r = \left\lceil \dfrac{N}{c} \right\rceil \qquad E_{\text{achieved}} = \dfrac{r\,c\,\Phi\cdot \mathrm{CU}\cdot \mathrm{LLF}}{A}

Columns along the long side.

Spacing check
max⁡ ⁣(Lc, Wr)≤SC⋅hrcLPD=count⋅wattsA\max\!\left(\dfrac{L}{c},\ \dfrac{W}{r}\right) \le \mathrm{SC}\cdot h_{rc} \qquad \mathrm{LPD} = \dfrac{\text{count}\cdot \text{watts}}{A}
Symbols
hrch_{rc}Room cavity height, luminaire plane to work planem
L, W, AL,\ W,\ ARoom length, width and floor aream, m²
RCR\mathrm{RCR}Room cavity ratio
EETarget average illuminancelux
Φ\PhiRated lumens per luminairelm
CU, LLF\mathrm{CU},\ \mathrm{LLF}Coefficient of utilization; light loss factor
c, rc,\ rLuminaire columns and rows
SC\mathrm{SC}Spacing criterion of the luminaire
LPD\mathrm{LPD}Lighting power densityW/m²
Room section with luminaire plane, work plane, and the room cavity height hrc between them.
Figure 1. Room cavities: ceiling cavity, room cavity and floor cavity.
Room plan with a grid of luminaires, spacing along length and width, and the limit SC times hrc.
Figure 2. Luminaire grid and maximum spacing.

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.

Lumen method, 20 × 10 m room, 500 lux lighting/lumen · Hand calculation

Pass

Source: Hand calculation from the lumen method equations — hrc = 3 − 0.8 = 2.2 m; RCR = 5·2.2·30/200 = 1.65; N = 500·200/(5000·0.6·0.8) = 41.67 → 42; grid 9 × 5 = 45; E = 45·2400/200 = 540 lux.

QuantityExpectedRokBenchErrorResult
rcr1.651.650%Pass
requiredCount42420%Pass
achievedLux5405400%Pass

7. Known issues and changes

See the Engineering Notes. Try the tool: Illuminance (Lumen Method).