Methods / Lumen Method
How RokBench checks this

Illuminance (Lumen Method)

The lumen (zonal cavity) method for average maintained illuminance and luminaire count.

1. What this check does

Computes the room cavity ratio, the number of luminaires needed for the target average maintained illuminance, a near-square grid that fits the room, and the illuminance that grid delivers. Optionally checks spacing against the luminaire spacing criterion and reports lighting power density.

2. Inputs used

3. Formulas and assumptions

hrc = ceiling height − work plane − suspension RCR = 5 · hrc · (L + W) / (L · W) N = E · A / (Φ · CU · LLF) rounded up Grid columns = round(√(N · L / W)) along the long side, rows = ⌈N / columns⌉ E_achieved = rows · columns · Φ · CU · LLF / A Spacing check: max(L / columns, W / rows) ≤ SC · hrc LPD = count · watts / A

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

Hand-calculated cases run on every change. See Validation.

7. Known issues and changes

See the Changelog. Try the tool: Illuminance (Lumen Method).

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.