Illuminance (Lumen Method)
The lumen (zonal cavity) method for average maintained illuminance and luminaire count.
1. What this check does
Computes the room cavity ratio, the number of luminaires needed for the target average maintained illuminance, a near-square grid that fits the room, and the illuminance that grid delivers. Optionally checks spacing against the luminaire spacing criterion and reports lighting power density.
2. Inputs used
- Room length, width and ceiling height; work plane height (default 0.76 m / 30 in) and suspension length.
- Target maintained illuminance, chosen by you from IES recommendations or the owner standard.
- Luminaire lumens and watts, coefficient of utilization (CU) from the photometric report at the computed RCR, light loss factor (LLF), and optionally the spacing criterion (SC).
3. Formulas and assumptions
Columns along the long side.
Symbols
| Room cavity height, luminaire plane to work plane | m | |
| Room length, width and floor area | m, m² | |
| Room cavity ratio | ||
| Target average illuminance | lux | |
| Rated lumens per luminaire | lm | |
| Coefficient of utilization; light loss factor | ||
| Luminaire columns and rows | ||
| Spacing criterion of the luminaire | ||
| Lighting power density | W/m² |
- Rectangular room with luminaires in a regular grid; the result is the average over the work plane.
- CU already reflects the room surface reflectances; RokBench does not reproduce CU tables or recommended illuminance values.
- LLF combines lamp lumen depreciation, luminaire dirt depreciation and ballast or driver factor as you choose.
4. What is NOT checked
- Uniformity and point-by-point illuminance.
- Glare and vertical illuminance.
- Emergency lighting levels and duration.
- Energy-code lighting power density limits.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- IES Lighting Handbook — lumen method and recommended illuminance
- ASHRAE/IES Standard 90.1 — lighting power density
- NFPA 101 Section 7.9 — emergency lighting
- Manufacturer photometric reports (CU tables, spacing criterion)
6. Validation cases
These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.
Lumen method, 20 × 10 m room, 500 lux lighting/lumen · Hand calculation
PassSource: Hand calculation from the lumen method equations — hrc = 3 − 0.8 = 2.2 m; RCR = 5·2.2·30/200 = 1.65; N = 500·200/(5000·0.6·0.8) = 41.67 → 42; grid 9 × 5 = 45; E = 45·2400/200 = 540 lux.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| rcr | 1.65 | 1.65 | 0% | Pass |
| requiredCount | 42 | 42 | 0% | Pass |
| achievedLux | 540 | 540 | 0% | Pass |
7. Known issues and changes
See the Engineering Notes. Try the tool: Illuminance (Lumen Method).