Methods / Ground Grid
How RokBench checks this

Ground Grid Step & Touch Voltage

The IEEE Std 80 simplified method for a uniformly spaced rectangular grid in uniform soil.

1. What this check does

Computes the tolerable touch and step voltages for the body weight and shock duration you choose, the grid resistance and ground potential rise, and the mesh (worst touch) and step voltages of a rectangular grid with equal spacing, then compares them.

2. Inputs used

3. Formulas and assumptions

Tolerable voltages

Surface layer
Cs=1−0.09 (1−ρ/ρs)2hs+0.09C_s = 1 - \dfrac{0.09\,(1 - \rho/\rho_s)}{2h_s + 0.09}
Touch
Etouch=(1000+1.5 Csρs) ktsE_{\text{touch}} = \bigl(1000 + 1.5\,C_s\rho_s\bigr)\,\dfrac{k}{\sqrt{t_s}}

k = 0.116 (50 kg) or 0.157 (70 kg).

Step
Estep=(1000+6 Csρs) ktsE_{\text{step}} = \bigl(1000 + 6\,C_s\rho_s\bigr)\,\dfrac{k}{\sqrt{t_s}}

Grid current and resistance

Decrement
Df=1+Tatf(1−e−2tf/Ta),Ta=X/R2πfD_f = \sqrt{1 + \dfrac{T_a}{t_f}\left(1 - e^{-2t_f/T_a}\right)}, \qquad T_a = \dfrac{X/R}{2\pi f}
Grid current
IG=Df Sf 3I0I_G = D_f\, S_f\, 3I_0
Resistance
Rg=ρ[1LT+120A(1+11+h20/A)]R_g = \rho\left[\dfrac{1}{L_T} + \dfrac{1}{\sqrt{20A}}\left(1 + \dfrac{1}{1 + h\sqrt{20/A}}\right)\right]

Sverak.

GPR
GPR=IG Rg\mathrm{GPR} = I_G\, R_g

Mesh and step voltage

Mesh / step
Em=ρ KmKi IGLMEs=ρ KsKi IGLSE_m = \dfrac{\rho\, K_m K_i\, I_G}{L_M} \qquad E_s = \dfrac{\rho\, K_s K_i\, I_G}{L_S}
Km
Km=12π[ln⁡ ⁣(D216hd+(D+2h)28Dd−h4d)+KiiKhln⁡8π(2n−1)]K_m = \dfrac{1}{2\pi}\left[\ln\!\left(\dfrac{D^2}{16hd} + \dfrac{(D+2h)^2}{8Dd} - \dfrac{h}{4d}\right) + \dfrac{K_{ii}}{K_h}\ln\dfrac{8}{\pi(2n-1)}\right]
Ks
Ks=1π[12h+1D+h+1−0.5 n−2D]K_s = \dfrac{1}{\pi}\left[\dfrac{1}{2h} + \dfrac{1}{D+h} + \dfrac{1 - 0.5^{\,n-2}}{D}\right]
Ki, Kh
Ki=0.644+0.148 n,n=nanbncnd,Kh=1+h/h0, h0=1 mK_i = 0.644 + 0.148\,n, \qquad n = n_a n_b n_c n_d, \qquad K_h = \sqrt{1 + h/h_0},\ h_0 = 1\ \mathrm{m}
Conductor size
Amm2=IkATCAP×10−4tc αr ρrln⁡K0+TmK0+TaA_{\mathrm{mm^2}} = \dfrac{I_{kA}}{\sqrt{\dfrac{\mathrm{TCAP}\times10^{-4}}{t_c\,\alpha_r\,\rho_r}\ln\dfrac{K_0 + T_m}{K_0 + T_a}}}

IEEE 80 Eq. 37 with the Table 1 material constants; I = Df × 3I0 (the conductor carries the whole fault), tc = fault duration, Ta = 40 °C unless entered.

Effective lengths
LM=LC+[1.55+1.22 LrLx2+Ly2]LRLS=0.75 LC+0.85 LRL_M = L_C + \left[1.55 + 1.22\,\dfrac{L_r}{\sqrt{L_x^2 + L_y^2}}\right] L_R \qquad L_S = 0.75\,L_C + 0.85\,L_R

LM = LC + LR when rods are not on the perimeter.

Symbols
ρ, ρs\rho,\ \rho_sSoil resistivity; surface layer (crushed rock) resistivityΩ·m
hs, Csh_s,\ C_sSurface layer thickness; surface layer derating factorm, —
kkBody constant: 0.116 for 50 kg, 0.157 for 70 kg
ts, tft_s,\ t_fShock duration; fault durations
X/R, f, TaX/R,\ f,\ T_aSystem X/R at the fault, frequency, DC time constant—, Hz, s
Df, SfD_f,\ S_fDecrement factor; current split factor
3I0, IG3I_0,\ I_GSymmetrical ground fault current; maximum grid currentA
A, Lx, LyA,\ L_x,\ L_yGrid area and side lengthsm², m
h, D, dh,\ D,\ dBurial depth, conductor spacing, conductor diameterm
LC, LR, Lr, LTL_C,\ L_R,\ L_r,\ L_TGrid conductor length, total rod length, one rod, total buried lengthm
LM, LSL_M,\ L_SEffective buried lengths for mesh and step voltagem
nnEffective number of parallel conductors (rectangle corrections na·nb·nc·nd)
Km, KsK_m,\ K_sSpacing factors for mesh and step voltage
Ki, Kii, KhK_i,\ K_{ii},\ K_hIrregularity factor; inner-conductor and depth corrections
Rg, GPRR_g,\ \mathrm{GPR}Grid resistance; ground potential riseΩ, V
Em, EsE_m,\ E_sMesh (worst touch) voltage; step voltageV
αr, ρr, K0, Tm, TCAP\alpha_r,\ \rho_r,\ K_0,\ T_m,\ \mathrm{TCAP}Conductor material constants: resistivity temperature coefficient, resistivity, 1/α0 − 20, fusing temperature, thermal capacity1/°C, µΩ·cm, °C, °C, J/cm³·°C
tc, Tat_c,\ T_aClearing time for conductor sizing; ambient temperatures, °C
Plan view of a rectangular ground grid with length Lx, width Ly, conductor spacing D and rods at the perimeter.
Figure 1. Ground grid plan: dimensions, conductor spacing and perimeter rods.
Cross-section showing the ground potential rise curve above a grid; a person touching a grounded structure (touch voltage) and a person walking (step voltage).
Figure 2. Touch and step voltage on the ground-potential profile during a fault.
Cross-section with a surface layer of thickness hs and resistivity rho-s over native soil of resistivity rho.
Figure 3. Crushed-rock surface layer over native soil.
Substation one-line showing fault current dividing between the ground grid and overhead shield wires or neutrals back to the source.
Figure 4. Only part of the fault current flows into the grid (split factor Sf).

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.

Square grid without ground rods, 70 × 70 m grounding/grid · Standard example

Pass

Source: IEEE Std 80-2013, Annex B, Example 1 (square grid without ground rods) — Input values only. Published tolerable voltages use Cs rounded to 0.74 and Em uses Km rounded to 0.89; RokBench carries full precision, hence the small differences. For comparison the standard quotes EPRI TR-100622 at 2.67 Ω and 984.3 V.

QuantityExpectedRokBenchErrorResult
gridResistanceOhm2.782.77570.155%Pass
meshVoltageV1002.11001.60.05%Pass
tolerableTouchV838.2840.50.274%Pass
tolerableStepV2686.62696.10.354%Pass
geometry.Km0.890.88960.045%Pass
geometry.Ki2.2722.2720%Pass
geometry.Ks0.4060.40610.025%Pass

Square grid with 20 perimeter ground rods, 70 × 70 m grounding/grid · Standard example

Pass

Source: IEEE Std 80-2013, Annex B, Example 2 (square grid with ground rods) — Input values only. Published values use Km rounded to 0.77; Rg by Equation (52) (Sverak), Em with the perimeter-rod effective length (Equation (91)). For comparison the standard quotes EPRI TR-100622 at 2.52 Ω, 756.2 V and 459.1 V.

QuantityExpectedRokBenchErrorResult
gridResistanceOhm2.752.75260.095%Pass
meshVoltageV747.4749.10.227%Pass
stepVoltageV548.9549.10.036%Pass
geometry.Km0.770.77170.221%Pass
geometry.Ki2.2722.2720%Pass
geometry.Ks0.4060.40610.025%Pass

Rectangular grid with 38 ground rods, 63 × 84 m grounding/grid · Standard example

Pass

Source: IEEE Std 80-2013, Annex B, Example 3 (rectangular grid with ground rods) — Input values only. Kii = 1 (grid with ground rods). The published Em back-calculates to LM = 2292.1 m, the perimeter-rod effective length of Equation (91), so onPerimeter is set. Published Em uses Km rounded to 0.77. For comparison the standard quotes EPRI TR-100622 at 2.28 Ω, 519.4 V and 349.7 V.

QuantityExpectedRokBenchErrorResult
gridResistanceOhm2.622.61850.057%Pass
meshVoltageV595.8593.60.369%Pass
geometry.conductorLengthM165916590%Pass
geometry.n11.3511.3440.053%Pass
geometry.Km0.770.76750.325%Pass
geometry.Ki2.3242.32290.047%Pass

7. Known issues and changes

See the Engineering Notes. Try the tool: Ground Grid Step & Touch Voltage.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.