Ground Grid Step & Touch Voltage
The IEEE Std 80 simplified method for a uniformly spaced rectangular grid in uniform soil.
1. What this check does
Computes the tolerable touch and step voltages for the body weight and shock duration you choose, the grid resistance and ground potential rise, and the mesh (worst touch) and step voltages of a rectangular grid with equal spacing, then compares them.
2. Inputs used
- Soil resistivity; optional surface layer resistivity and thickness.
- Grid length and width, conductor spacing, burial depth and conductor diameter; optional ground rods (count, length, on the perimeter or not).
- Symmetrical ground fault current 3I0, split factor Sf, fault and shock duration, optional X/R.
- Body weight 50 or 70 kg.
- Optional conductor material and ambient temperature for the conductor sizing check.
3. Formulas and assumptions
Tolerable voltages
k = 0.116 (50 kg) or 0.157 (70 kg).
Grid current and resistance
Sverak.
Mesh and step voltage
IEEE 80 Eq. 37 with the Table 1 material constants; I = Df × 3I0 (the conductor carries the whole fault), tc = fault duration, Ta = 40 °C unless entered.
LM = LC + LR when rods are not on the perimeter.
Symbols
| Soil resistivity; surface layer (crushed rock) resistivity | Ω·m | |
| Surface layer thickness; surface layer derating factor | m, — | |
| Body constant: 0.116 for 50 kg, 0.157 for 70 kg | ||
| Shock duration; fault duration | s | |
| System X/R at the fault, frequency, DC time constant | —, Hz, s | |
| Decrement factor; current split factor | ||
| Symmetrical ground fault current; maximum grid current | A | |
| Grid area and side lengths | m², m | |
| Burial depth, conductor spacing, conductor diameter | m | |
| Grid conductor length, total rod length, one rod, total buried length | m | |
| Effective buried lengths for mesh and step voltage | m | |
| Effective number of parallel conductors (rectangle corrections na·nb·nc·nd) | ||
| Spacing factors for mesh and step voltage | ||
| Irregularity factor; inner-conductor and depth corrections | ||
| Grid resistance; ground potential rise | Ω, V | |
| Mesh (worst touch) voltage; step voltage | V | |
| Conductor material constants: resistivity temperature coefficient, resistivity, 1/α0 − 20, fusing temperature, thermal capacity | 1/°C, µΩ·cm, °C, °C, J/cm³·°C | |
| Clearing time for conductor sizing; ambient temperature | s, °C |
- Uniform soil. The simplified equations apply to grids with n up to 25, depth 0.25–2.5 m, spacing above 2.5 m and conductor diameter small compared with depth; outside that range a warning asks for a computer analysis.
- The split factor Sf is entered by you — it depends on overhead ground wires, cable sheaths and remote grounds.
- Without X/R the decrement factor is 1.0, which understates the current for short fault durations.
- Worst-case touch is taken as the mesh voltage at the center of a corner mesh.
- Conductor sizing follows IEEE 80 Eq. 37 with the Table 1 material constants (copper soft- and hard-drawn, copper-clad steel 40 % and 30 %, EC aluminum, 1020 steel), for the whole fault current with the decrement factor over the fault duration, from 40 °C ambient unless entered.
4. What is NOT checked
- Two-layer or multilayer soil.
- Touch voltage at the fence or outside the grid, and transferred potentials.
- Connection (joint) temperature limits; the sizing check uses the conductor fusing temperature. Corrosion allowance and mechanical strength.
- Irregular grids and unequal spacing.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- IEEE Std 80 — guide for safety in AC substation grounding
- IEEE Std 81 — measuring earth resistivity and ground impedance
- NEC 2023 Article 250 (equipment grounding, context)
6. Validation cases
These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.
Square grid without ground rods, 70 × 70 m grounding/grid · Standard example
PassSource: IEEE Std 80-2013, Annex B, Example 1 (square grid without ground rods) — Input values only. Published tolerable voltages use Cs rounded to 0.74 and Em uses Km rounded to 0.89; RokBench carries full precision, hence the small differences. For comparison the standard quotes EPRI TR-100622 at 2.67 Ω and 984.3 V.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| gridResistanceOhm | 2.78 | 2.7757 | 0.155% | Pass |
| meshVoltageV | 1002.1 | 1001.6 | 0.05% | Pass |
| tolerableTouchV | 838.2 | 840.5 | 0.274% | Pass |
| tolerableStepV | 2686.6 | 2696.1 | 0.354% | Pass |
| geometry.Km | 0.89 | 0.8896 | 0.045% | Pass |
| geometry.Ki | 2.272 | 2.272 | 0% | Pass |
| geometry.Ks | 0.406 | 0.4061 | 0.025% | Pass |
Square grid with 20 perimeter ground rods, 70 × 70 m grounding/grid · Standard example
PassSource: IEEE Std 80-2013, Annex B, Example 2 (square grid with ground rods) — Input values only. Published values use Km rounded to 0.77; Rg by Equation (52) (Sverak), Em with the perimeter-rod effective length (Equation (91)). For comparison the standard quotes EPRI TR-100622 at 2.52 Ω, 756.2 V and 459.1 V.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| gridResistanceOhm | 2.75 | 2.7526 | 0.095% | Pass |
| meshVoltageV | 747.4 | 749.1 | 0.227% | Pass |
| stepVoltageV | 548.9 | 549.1 | 0.036% | Pass |
| geometry.Km | 0.77 | 0.7717 | 0.221% | Pass |
| geometry.Ki | 2.272 | 2.272 | 0% | Pass |
| geometry.Ks | 0.406 | 0.4061 | 0.025% | Pass |
Rectangular grid with 38 ground rods, 63 × 84 m grounding/grid · Standard example
PassSource: IEEE Std 80-2013, Annex B, Example 3 (rectangular grid with ground rods) — Input values only. Kii = 1 (grid with ground rods). The published Em back-calculates to LM = 2292.1 m, the perimeter-rod effective length of Equation (91), so onPerimeter is set. Published Em uses Km rounded to 0.77. For comparison the standard quotes EPRI TR-100622 at 2.28 Ω, 519.4 V and 349.7 V.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| gridResistanceOhm | 2.62 | 2.6185 | 0.057% | Pass |
| meshVoltageV | 595.8 | 593.6 | 0.369% | Pass |
| geometry.conductorLengthM | 1659 | 1659 | 0% | Pass |
| geometry.n | 11.35 | 11.344 | 0.053% | Pass |
| geometry.Km | 0.77 | 0.7675 | 0.325% | Pass |
| geometry.Ki | 2.324 | 2.3229 | 0.047% | Pass |
7. Known issues and changes
See the Engineering Notes. Try the tool: Ground Grid Step & Touch Voltage.