Methods / Generator Sizing
How RokBench checks this

Emergency Generator Sizing

The PG1–PG3 method: running load, voltage dip on motor starting, and instantaneous engine load.

1. What this check does

Takes the loads a generator must carry, including motors and how they start, and computes three required capacities. PG1 covers the running load; PG2 keeps the terminal voltage dip within the allowed value when the motor with the largest starting kVA starts; PG3 keeps the engine within its short-time overload while that start happens with everything else running. The generator must meet the largest of the three.

2. Inputs used

3. Formulas and assumptions

Input kW P = Σ kW · qty · demand / η kVAR Q = Σ P_i · tan(acos PF_i) PG1 = max( √(P² + Q²), P / cosθG ) Starting kVA Q_L = k_start · kW / (η · PF) for one unit of the motor k_start = LR (DOL), LR/3 (star-delta), LR·tap² (autotransformer), current limit (soft starter, VFD) PG2 = Q_L · Xd'' · (1 − ΔV) / ΔV (from ΔV = Xd''·q / (1 + Xd''·q), q = Q_L / PG) PG3 = ( P − P_run,m + Q_L,m · cosθs ) / (K · cosθG) m = the motor whose start adds the most kW Fire pump = Q_L,fp · Xd'' · 0.85 / 0.15 (dip ≤ 15%, when a fire pump is marked) Required kVA = max(PG1, PG2, PG3, fire pump); kW = kVA · cosθG → next listed rating

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

Hand-calculated cases run on every change. See Validation.

7. Known issues and changes

See the Changelog. Try the tool: Emergency Generator Sizing.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.