Methods / Cable Check
How RokBench checks this

Cable Check

What the check does, the formulas behind it, and what it deliberately leaves out.

1. What this check does

For a cable you have already chosen, RokBench computes the load current, compares the design current per set with the cable's allowable ampacity, and estimates the running and motor-starting voltage drop along the cable. It reports what does not hold up and why. It does not select a cable, although it may point to the smallest size in the same cable family that would pass.

2. Inputs used

3. Formulas and assumptions

Load current

Three-phase
I=P3 V PF ηI=S3 VI = \dfrac{P}{\sqrt{3}\,V\,\mathrm{PF}\,\eta} \qquad I = \dfrac{S}{\sqrt{3}\,V}

V line-to-line. η applies to kW and HP inputs.

Single-phase
I=PV PF ηI=SVI = \dfrac{P}{V\,\mathrm{PF}\,\eta} \qquad I = \dfrac{S}{V}
HP
P=HP×745.7 WP = \mathrm{HP} \times 745.7\ \mathrm{W}

Blank efficiency uses the DOE minimum for the rating (10 CFR 431.25).

Design current and ampacity

Design current per set
Id=k INI_d = \dfrac{k\, I}{N}

k = 1.25 for motor and continuous loads, 1.0 otherwise; N = parallel sets.

Allowable ampacity
Ia=Itable⋅Ft⋅FgI_a = I_{\text{table}} \cdot F_t \cdot F_g
Motor
Id≤IaI_d \le I_a

NEC 430.22: 125 % of motor current against the corrected ampacity.

Continuous, non-continuous
Id≤Itable, 75 °CandIN≤IaI_d \le I_{\text{table, 75 °C}} \quad\text{and}\quad \dfrac{I}{N} \le I_a

NEC 210.19(A)(1), 215.2(A)(1): 125 % before correction at the termination column (110.14(C)), 100 % after correction.

Temperature factor
Ft=Tc−Ta′Tc−TaF_t = \sqrt{\dfrac{T_c - T_a'}{T_c - T_a}}

NEC 310.15(B)(1). Tc conductor rating, Ta′ design ambient, Ta basis ambient; Fg grouping adjustment.

Voltage drop

Drop
ΔV=c I L1000 N (Rcos⁡φ+Xsin⁡φ)\Delta V = \dfrac{c\, I\, L}{1000\,N}\,\bigl(R\cos\varphi + X\sin\varphi\bigr)

c = √3 three-phase, 2 single-phase; R, X in Ω per 1000 ft per conductor; L in ft.

Percent
ΔV%=ΔVV×100\Delta V\% = \dfrac{\Delta V}{V} \times 100

Starting drop: same formula with the starting current and starting power factor.

Symbols
PPReal power of the load (kW, or HP converted)kW
SSApparent powerkVA
VVSystem voltage, line-to-line for three-phaseV
PF, φ\mathrm{PF},\ \varphiPower factor and its angle, PF = cos φ
η\etaMotor or equipment efficiency
IILoad currentA
kkContinuous or motor load multiplier (1.25 or 1.0)
NNNumber of parallel sets
Itable, IaI_{\text{table}},\ I_aTable ampacity, allowable ampacity after correctionA
Ft, FgF_t,\ F_gTemperature correction factor, grouping adjustment factor
Tc, Ta, Ta′T_c,\ T_a,\ T_a'Conductor rating, table basis ambient, design ambient°C
cc√3 for three-phase, 2 for single-phase
LLOne-way circuit lengthft
R, XR,\ XConductor resistance and reactanceΩ per 1000 ft
Phasor diagram with receiving voltage, current at angle phi, and the I·R and I·X drops.
Figure 1. Voltage drop as the projection of I·R and I·X on the sending-end voltage.
Cross-section of a three-conductor cable showing conductors, insulation, shield and jacket; beside it two parallel sets.
Figure 2. Three-conductor cable cross-section and parallel sets.
Block diagram: table ampacity times temperature factor times grouping factor gives allowable ampacity; load current times 1.25 divided by sets gives design current; the two are compared.
Figure 3. From table ampacity to allowable ampacity, compared with design current.
Three small sketches: cables in conduit, cables in an underground duct bank, and a cable in free air.
Figure 4. Installation methods: raceway, underground duct, free air.

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

Hand-calculated cases run on every change. Published textbook cases will be listed on the Validation page.

7. Known issues and changes

See the Engineering Notes. Try the tool: Cable Check.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.