Methods / Battery Sizing
How RokBench checks this

Stationary Battery Sizing

The IEEE 485 period method: the duty cycle is cut into sections, each change in current is weighted by a capacity rating factor, and the largest section sets the size.

1. What this check does

Takes the DC duty cycle as periods of current in order, works out the number of cells and the end-of-discharge voltage per cell, computes the uncorrected capacity each section needs, takes the largest, and applies the temperature, aging and design-margin factors to give the rated capacity at the 8-hour rate.

2. Inputs used

3. Formulas and assumptions

Cells and end voltage

Cells
N=round ⁣(VnomVcell)Vend=Vmin⁡NN = \mathrm{round}\!\left(\dfrac{V_{\text{nom}}}{V_{\text{cell}}}\right) \qquad V_{\text{end}} = \dfrac{V_{\min}}{N}

V_cell = 2.0 V lead-acid, 1.2 V nickel-cadmium.

Section method

Section capacity
Fs=∑p=1s(Ap−Ap−1) K(Tp→s)F_s = \sum_{p=1}^{s} \bigl(A_p - A_{p-1}\bigr)\, K\bigl(T_{p \to s}\bigr)

T = time from the start of period p to the end of section s; A0 = 0.

Rating factor
K(t)=C8It(manufacturer)K(t)≈8(t8 h)1/n(estimate)K(t) = \dfrac{C_8}{I_t} \quad\text{(manufacturer)} \qquad K(t) \approx 8\left(\dfrac{t}{8\ \mathrm{h}}\right)^{1/n} \quad\text{(estimate)}

n = Peukert exponent, default 1.25.

Required
Creq=max⁡sFs×kT×1.25×kmarginC_{\text{req}} = \max_s F_s \times k_T \times 1.25 \times k_{\text{margin}}

Rated capacity at the 8-hour rate; kT from IEEE 485 Table 1 for the lowest electrolyte temperature.

Symbols
Vnom, Vmin⁡, Vcell, VendV_{\text{nom}},\ V_{\min},\ V_{\text{cell}},\ V_{\text{end}}Nominal and minimum DC system voltage; nominal and end-of-discharge voltage per cellV
NNNumber of cells
Ap, Tp→sA_p,\ T_{p \to s}Current in period p; time from its start to the end of section sA, h
K(t), C8, ItK(t),\ C_8,\ I_tCapacity rating factor; rated capacity at the 8-hour rate; current the cell delivers for th, Ah, A
nnPeukert exponent used for the estimate
Fs, CreqF_s,\ C_{\text{req}}Uncorrected capacity of section s; required rated capacityAh
kT, kmargink_T,\ k_{\text{margin}}Temperature correction; design margin (aging 1.25 is fixed)

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.

125 V switchgear battery, four-period duty cycle with an entered K curve battery/sizing · Hand calculation

Pass

Source: Hand calculation of the IEEE 485 section method with the K curve entered as points (linear between points) — Periods 120 A/1 min, 15 A/59 min, 40 A/120 min, 100 A/1 min. K points (min → h): 1 → 0.9, 15 → 1.6, 60 → 2.8, 180 → 5.0, 480 → 8. S1 = 120·0.9 = 108. S2 (60 min) = 120·2.8 − 105·K(59) = 336 − 291.2 = 44.8. S3 (180) = 120·5.0 − 105·K(179) + 25·K(120) = 600 − 523.1 + 97.5 = 174.4. S4 (181) = 120·K(181) − 105·5.0 + 25·K(121) + 60·0.9 = 601.2 − 525 + 97.96 + 54 = 228.2 → × 1.25 × 1.10 = 313.8 Ah. 125/2 = 62.5 → 63 cells, 105/63 = 1.667 V/cell.

QuantityExpectedRokBenchErrorResult
cells63630%Pass
endVoltagePerCell1.6671.6670%Pass
uncorrectedAh228.2228.20%Pass
governingSection440%Pass
requiredAh3143140%Pass

7. Known issues and changes

See the Changelog. Try the tool: Stationary Battery Sizing.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.