Motor Starting Voltage Dip
The constant-impedance method for the bus dip and the motor terminal voltage while a motor starts.
1. What this check does
Builds the source and transformer impedance to the motor bus, adds the existing load as a fixed impedance and the starting motor as its locked-rotor impedance behind the feeder, and solves the voltage divider. It reports the bus voltage before and during the start, the dip other loads see, and — for across-the-line starting — the motor terminal voltage and the share of locked-rotor torque it leaves.
2. Inputs used
- Motor bus voltage; utility short-circuit MVA and X/R, or an infinite bus; optional transformer kVA, %Z and X/R.
- Optional load already on the bus (kVA and power factor) and the feeder to the motor (length, R and X per conductor, parallel sets).
- Motor output (hp or kW), efficiency, running power factor, starting method with its locked-rotor multiple, autotransformer tap or current limit, and starting power factor.
- Criteria: maximum bus dip and minimum motor voltage while starting.
3. Formulas and assumptions
Impedances on the motor bus voltage
R = |Z|/√(1 + (X/R)²), X = R·X/R. Feeder Z_c = (R + jX)·length / parallel sets.
k_start = LR (DOL), LR/3 (star-delta), LR·tap² (autotransformer), current limit (soft starter, VFD).
Voltages
Compared with the maximum bus dip; Vm with the minimum motor voltage.
Symbols
| Motor bus line-to-line voltage | V | |
| Utility short-circuit power; transformer rating and impedance | MVA, kVA, % | |
| Source-plus-transformer impedance; feeder impedance | Ω | |
| Starting motor impedance; existing load impedance | Ω | |
| Motor rated output, efficiency, running power factor | kW, —, — | |
| Line-side starting kVA, starting power factor, starting multiple | kVA, —, — | |
| Bus voltage before and during the start; motor terminal voltage | per unit | |
| Available starting torque; locked-rotor torque at rated voltage | % |
- The starting motor is a constant impedance drawing its starting kVA at rated voltage and the starting power factor; at lower voltage its current falls in proportion, which is how a locked rotor behaves.
- Line-side starting kVA multiples: across-the-line = locked-rotor multiple, star-delta = one third of it, autotransformer = multiple × tap², soft starter and VFD = the current limit. With a reduced-voltage starter only the line side is assessed.
- Available starting torque scales with the square of the motor voltage (V² × locked-rotor torque).
- The existing load is a constant impedance, and the dip is measured against the bus voltage just before the start.
- Default criteria are RokBench assumptions: 10 % bus dip and 80 % motor voltage while starting. Use your project, utility and equipment criteria.
4. What is NOT checked
- Acceleration time and the motor and load torque curves (a dynamic motor-starting study).
- Transformer tap changers, voltage regulators and capacitor switching during the start.
- Generator sources — the transient reactance and voltage regulator govern there (see Emergency Generator Sizing).
- Flicker limits for repeated starts and utility point-of-common-coupling requirements.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- IEEE Std 399 (Brown Book) and IEEE Std 3002.7 — motor-starting studies
- NEMA MG 1 — motor performance at reduced voltage, locked-rotor code letters
- IEEE Std 1453 / IEC 61000-3-3 — voltage fluctuation and flicker
- NEC 2023 Article 430 — motor circuits (context)
6. Validation cases
These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.
150 kW motor started across the line on a 1500 kVA, 5.75 % Z transformer motor/starting · Hand calculation
PassSource: Hand calculation from the constant-impedance equations on the Methods page — Zt = 0.0575 · 480² / 1.5 MVA = 8.832 mΩ at X/R 6 (R 1.452, X 8.712 mΩ). Running 150/(0.95·0.88) = 179.4 kVA, starting 6 × = 1076.6 kVA → Zm = 480²/1076.6 kVA = 0.21401 Ω at PF 0.3 (R 64.20, X 204.15 mΩ). V = |Zm|/|Zt + Zm| = 0.21401/0.22276 = 0.9607 → dip 3.93 %; torque ≈ 0.9607² = 92.3 % of locked-rotor.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| startingKva | 1076.6 | 1076.6 | 0% | Pass |
| busDuringPercent | 96.07 | 96.07 | 0% | Pass |
| busDipPercent | 3.93 | 3.93 | 0% | Pass |
| torquePercentOfLocked | 92.3 | 92.3 | 0% | Pass |
7. Known issues and changes
See the Changelog. Try the tool: Motor Starting Voltage Dip.