Ground Rod and Wire Resistance
Estimating the resistance of driven rods, a buried horizontal ground wire, and both together in uniform soil.
1. What this check does
Estimates the resistance to remote earth of one driven rod with the Dwight formula, of several rods by the average-potential method with a line-source mutual resistance, of a buried horizontal wire with Dwight's horizontal-wire formula, and of rods and wire together as parallel resistances.
2. Inputs used
- Electrode type: rods, a buried horizontal wire, or both.
- Soil resistivity (Ω·m).
- Rods: length, diameter, number, spacing and arrangement (line or ring).
- Wire: total length, burial depth and conductor size (AWG, kcmil or mm²; the radius of a solid conductor of the same area is used).
3. Formulas and assumptions
Rods
Dwight. a = rod radius.
Average-potential method.
Horizontal wire and combination
Total length 2L, radius a, burial depth s/2 (Dwight, as given in IEEE 142).
Parallel, neglecting mutual interaction.
Symbols
| Soil resistivity | Ω·m | |
| Rod length; for a horizontal wire, half its length | m | |
| Rod or wire radius | m | |
| Distance between two rods (mutual resistance) | m | |
| Number of rods | ||
| Resistance of one rod; mutual resistance between rods i and j | Ω | |
| Twice the burial depth of the horizontal wire | m |
- Uniform soil of the resistivity entered.
- The mutual term is the potential of a line current source with its image; it is less accurate when rods are closer than about twice their length.
- The wire formula assumes the wire is long compared with twice its burial depth; a short wire is flagged.
- Rods and wire are combined in parallel, the usual practice. Because both use the same soil the real value is somewhat higher, between the parallel value and the lower of the two alone; the tool reports that range.
- For a meshed grid with rods, the IEEE 80 Ground Grid tool (Sverak and Schwarz equations) is the better model.
4. What is NOT checked
- Layered soil, seasonal moisture and frost.
- Step and touch voltage (see Ground Grid).
- Conductor sizing for fault current.
- Lightning and high-frequency impedance.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- NEC 2023 250.53(A)(2), 250.53(A)(3) — supplemental electrode and rod spacing
- IEEE Std 142 — grounding of industrial and commercial power systems (Dwight formulas)
- H. B. Dwight, Calculation of Resistances to Ground (1936)
- IEEE Std 81 — measuring earth resistivity and ground impedance
6. Validation cases
These worked examples run through the engine on every change; the expected values come from the cited source. All cases: Validation.
Buried horizontal wire, 100 m of 4/0 AWG at 0.8 m in 100 Ω·m soil ground/rod · Hand calculation
PassSource: Hand calculation from Dwight's buried horizontal wire formula (as given in IEEE Std 142) — 4/0 AWG = 211.6 kcmil = 107.22 mm² → a = √(107.22/π) = 5.842 mm; L = 50 m, s = 1.6 m. R = 100/(4π·50)·[ln(200/0.005842) + ln(200/1.6) − 2 + 1.6/100 − 1.6²/(16·50²) + 1.6⁴/(512·50⁴)] = 2.114 Ω.
| Quantity | Expected | RokBench | Error | Result |
|---|---|---|---|---|
| wireOhm | 2.114 | 2.11 | 0.189% | Pass |
| totalOhm | 2.114 | 2.11 | 0.189% | Pass |
7. Known issues and changes
See the Engineering Notes. Try the tool: Ground Rod and Wire Resistance.